Roll over image to zoom in

Sterilight® Platinum "SPV" 14.9 GPM Ultraviolet Water Sterilizer System

  •   Model # SPV-950
  •   UPC 773058096430
  •   Brand Sterilight
Filtered Water Benefits the Whole Family
Standard Dosage
US Public Health Standard - EPA16mJ (high capacity stated)
Industry/Manufacturers Standard30mJ (primary capacity stated - top of page)
NSF Standard40mJ (lowest capacity stated)
Contaminant Dosage required to sterilize
(mJ/cm2) 99% Effectiveness
Cryptosporidium parvum oocysts8
Giardia lamblia cysts (Beaver fever)< 10
Vibrio cholerae (Cholera)3
Shigella dysenteriae (Dysentery)3
E.coli (Escherichia coli O157:H7)6
Salmonella typhi (Typhoid fever)9
Shigella sonnei9
Legionella pneumophila (Legionaires' disease)10
Salmonella enteritidis (causes gastroenteritis)10
Hepatitis A virus16 - 30
Poliovirus Type 121 - 30
Coxsackie B5 virus30
Rotavirus SA1131 - 36

It is strongly recommended (by all UV manufacturers) for maximum efficiency of your UV Sterilization, that you pre-filter your water with a 5 Micron sediment cartridge.

Do not connect plastic pipe or tubing directly to the UV system because the UV light will break down plastic over time. The best way to make the connection is with Dielectric Unions that allow for a connection from stainless steel to copper, that will not corrode.

Pre-Filter Required
The most suitable replacement for this is the
UV Max PRO 20 (650653)

Need a replacement UV lamp? This system uses the
Sterilight S950RL-HO Replacement Lamp

The Sterilight® Platinum™ "SPV" series carry NSF/ANSI Standard 55, Class A certification. A total of eight systems are available with flow rates from 2.6 to 14.9 gpm. Whether you are looking for a point-of-use disinfection system or a high-flow point-of-entry system, Sterilight's "SPV" Platinum systems have you covered.

Applications include private wells, camp grounds, hotels, bottlers, aquaculture, hospitals, food, cottages, restaurants, breweries, water systems, laboratories, marine, pharmaceutical, dairies and many other applications.

Sterilight® UV Systems Warranty:

  • 7-Year Warranty on the Stainless Steel UV Reactor
  • 1-Year Warranty on UV lamps, quartz sleeves and sensor
  • 5-Year Pro-rated Warranty on all other components


  • 56.6 L/min (14.9 gpm) capacity (dose 40mJ/cm2)
  • Sterilume-HO UV lamps
  • Optional solenoid available
  • Easy lamp replacement without having to disconnect the water supply
  • Visual lamp-on indicators and audible lamp failure indicator
  • Seven year warranty on reactor chamber for unparalleled protection
  • Polished 316 L stainless reactor chamber
  • Maximum UV output with the highest quality quartz sleeve
  • 3/4" FPT & 1" MPT connections for quick and easy installation
  • 99.99% destruction of bacteria, virus and protozoan cysts (Giardia Lamblia and Cryptosporidium) at rated flow
  • Nature's way to protect your water without the addition of harmful chemicals
  • Open end quartz sleeve and aluminum gland nuts for optimum operating temperature and sealing efficiency

Sterilight® Platinum Series Flow Rate vs UV Dose Sizing Your System

The UV dose delivered by a given reactor is dependent on many factors, including water quality and flow rate. NSF/ANSI Standard 55 requires that the UV system deliver a minimum UV fluence of 40 mJ/cm2 at the alarm set-point. The accompanying graph shows how the delivered fluence will be affected at varying UV transmittance levels.